FAQs
I wish to use the AutoLearn feature on my new installations for all my FWC-FSLC devices. When I use the AutoLearn feature, it automatically assigns my SLC devices to the zone number (for example, a smoke detector addressed as #1 is assigned to zone #1 if using AutoLearn). Some of my installations also require the GEMC-F8ZCPIM Conventional 8 Fire Zone Expander Plug in Module. Is there a way to enable the GEMC-F8ZCPIM and use the AutoLearn feature?
No, after the control panel is programmed, the AutoLearn feature can no longer be used. A workaround would be to not use SLC addresses one through eight; start your SLC addressing at number nine, then after AutoLearning and uploading the control panel, enable the GEMC-F8ZCPIM in the PCD-Windows System Options screen. If needed, SLC addresses one through eight can be used later with other zones.