Answer:
To program a "Panel Relay Fire Trouble Relay" to monitor the status of the relays within the fire alarm panel (terminals 10, 11, and 12) to trigger a trouble signal by a loss of power:
...
View Answer
Answer:
Yes. The FW-2S 2-Wire Smoke Detectors can be used with UL Listed control panels without using the integral sounder, thus eliminating the need for using the FW-RM1 Reversing Module with NAPCO Gemini control panels or using the GEMC-SDW...
View Answer
Answer:
No, it is not possible for a user to add or delete user codes through keypad programming. The only similar user code function available is to update a known user code already programmed in system.
View Answer
Answer:
Models: All FireLink, Firewolf* and GEMC* Fire Panels (FL-xxx, FLX2-xxx, GEMC-FW-xxx, GEMC-COMBOxxx)
...
View Answer
Answer:
Connect the purple wire from the FW-RM1 to the control panel positive Bell terminal.
...
View Answer
Answer:
No, after the control panel is programmed, the AutoLearn feature can no longer be used. A workaround would be to not use SLC addresses one through eight; start your SLC addressing at number nine, then after AutoLearning and uploading the...
View Answer
Answer:
Turn on a blow dryer to its highest "heat" setting and hold 12 inches from the top side inlets of the FWC-FSLC-HEAT detector. Maintain the hot air flow into the inlets until the lights turn red and unit goes into alarm. Turn off the...
View Answer