FAQs
How do I wire a 2-wire smoke detector using the Napco Firewolf FW-RM1 Reversing Module?
- Connect the purple wire from the FW-RM1 to the control panel positive Bell terminal.
- Connect the black wire from the FW-RM1 to the control panel negative Bell terminal.
- Connect the red wire from the FW-RM1 to the control panel AUX Power positive (+) terminal.
- Connect the orange wire from the FW-RM1 to the control panel 2-wire Fire Power (FIRE PWR) negative (-) or active low terminal.
- Connect the yellow wire to the control panel resettable Fire Power (FIRE PWR) positive (+) or active high terminal.
- Connect the FW-RM1 Zone positive (+) terminal to the smoke detector positive (+) terminal.
- Connect the FW-RM1 Zone negative (-) terminal to the smoke detector negative (-) terminal.
- Wire the 2.2K end-of-line-resistor (EOLR) at the end of the line of the smoke loop.
- On the control panel motherboard, place the JP7 jumper (or the JP3 jumper, as determined by the control panel model) into the 2-Wire Fire position for the wired zone.