My Gemini GEM-P801 control panel is going into alarm correctly, but is not dialing out. What programming addresses should be checked?
Check address 34 to ensure zones are programmed to report on Telco #1. If zones are correctly programmed to report on Telco #1 but are still not reporting, check address 79 (Abort Delay Zone Mask). If all zones are turned on, they are programmed for Abort Delay.
Proceed as follows:
- Enter Dealer Keypad Program Mode.
- Turn all zones off by pressing the zone numbers on the keypad.
- Exit Dealer Keypad Program Mode.
- Arm the system and test the zones. Ensure that the red light on the control panel lights and the zones report correctly.