My State requires distinct NAC indications for Fire and Carbon Monoxide alarm conditions. Can a GEMC NAC circuit sound different alarm cadences by zone?
An initiating zone can be individually programmed, using PCD-Windows Quickloader software, to activate one of thirty available coded alarms/cadences on the NAC circuits.
Program as follows:
1. Open the NAC/Output Assignment screen, click the NAC/Output Options tab, then check the Coded Alarms by Zone checkbox and the Coded Alarm column appears in the Zone Assignment screen (Ctrl + Shift + Z). Select a cadence for each zone, as required.
2. Program at least one silence-able NAC output (typically all NAC outputs) for Enable Cadence (in the NAC/Output Assignment screen, click the NAC/Output Assignments tab, then check the Enable checkbox for the selected output in the Cadence column.