FAQs
My Fire Alarm Control Panel installation requires the FACP to communicate through the telco line with cellular backup. What are the telephone line and StarLink communicator connections to the FACP?
For installations that require the FACP to communicate through the telco line with cellular backup, the telephone line must be connected to the FACP Telco 1 (DACT 1) and the StarLink communicator TELCO SECONDARY to the FACP Telco 2 (DACT 2), as shown in the diagram below.