When "Panel Access" is enabled, pressing the Access Code on the keypad energizes the control panel Aux Output for a specified duration. How do I program PCD-Windows Quickloader for this functionality?
Program PCD-Windows Quickloader as follows:
- System Assignment > System Options: Check Access Control on Burg PGM1 Output.
- System Assignment > Time Selection: Enter the amount of time you want the Aux Relay to remain energized. Example: "10 Seconds". IMPORTANT: A time MUST be selected.
- Keypad Assignment > Keypad Assignment: Enable "Panel Access" for all keypads that can be used to energize the Aux Relay.
- User Assignment > User/System Codes: At the bottom of the dialog, type a control panel Access Code in the field provided.
- Keypad Assignment > Keypad Reporting and Outputs: Click the "Auxiliary" pull-down list and assign to an Area.
Operation: At the system keypad, press the Access Code followed by ENTER (or ON/OFF). Note: Wire connections to 8 (+) & 14 (-). In the default state, the "AUX RELAY" produces 12VDC. If you need dry contacts, cut jumper "A".