I'm trying to use the Auto Learn feature to enroll my Firewolf FWC-FSLC devices with a GEMC-BSLC Burglary Signaling Line Circuit Module wired to the GEMC control panel. Will the GEMC-BSLC connection cause an issue when trying to Auto Learn Fire SLC devices?
Yes, a GEMC-BSLC Burglary Signaling Line Circuit Module wired to the GEMC control panel could cause an issue when trying to Auto Learn Fire SLC devices, as follows:
If the control panel is new (or cold started), the control panel will look for SLC devices attached to ports 1 and 2, but will be unable to determine which type (Fire or Burglary) are connected.
The solution: Simply disconnect the GEMC-BSLC PC board before Auto Learning Fire SLC devices. When finished, simply reconnect the GEMC-BSLC PC board and upload and program the Burglary SLC devices.