My AHJ (authority having jurisdiction) requires the HVAC units to have an independent means of restoration separate from a Fire alarm system restoration. Can the Gemini C-Series (GEMC) control panels be programmed to allow this?
Yes. In the PCD-Windows Quickloader NAC/Output Assignment screen (NAC/Output Assignments tab), program the Fire relay outputs as Supplemental.
After the Fire alarm has been restored, unlock the GEMC-FK1 Fire keypad by first pressing a valid Fire code followed by ENTER. Scroll through the keypad menu until the display reads Reset Supplemental Output, then press ENTER. If the control panel is running firmware version V83A6, Supplemental outputs may be restored by pressing and holding zero (after the GEMC-FK1 Fire keypad is unlocked).