I installed a GEMC "Burg-only" control panel. When the system sends a Test Timer report to the central station, the central station receives an E608 (Test Timer with Fire Trouble Present report) instead of an E602 (standard Test Timer report). I checked the control panel programming and nothing is programmed for Fire or for Area #1. Why is the control panel sending an E608 code?
Although the system is "Burg-only", the 2.2k EOL resistors must still be installed across the NAC circuits. In PCD-Windows Quickloader, click Tools, Panel Error Check and review the control panel status to see if there any other Fire Troubles present.