How do I program the Test Timer feature with the GEM-P816, GEM-P1632, GEM-P1664 Control Panels?
If the Test Timer feature is programmed, an automatic test report will be transmitted to the central station on the scheduled day(s) at the scheduled time (UL installations require a report at least every 24 hours).
1. In PCD-Windows Quickloader, open the System Assignment screen, Time Selection tab. In the Test Timer Time-of-Day field, type the time (in 24-hour military format) you wish the report to be sent. Select a day in the Test Timer Day-of-Week field for a weekly test report, or click to highlight every day of the week for daily test reports.
2. Then open the System Reporting and Outputs tab and for the Test Timer report, check the Report on Alarm Telco 1.