With my StarLink communicator operating in Direct Mode, why are the 780 heartbeat signals not being displayed in the NAPCO NOC web portal (www.NapcoNOC.com)?
A Contact ID Event Code 780 'heartbeat' signal (also called a supervisory or polling signal) is an automated, periodic message sent between the control panel, the system devices, and the central station to verify these connections are working correctly.
By design, when a StarLink communicator is operating in Direct Mode, these 780 heartbeat signals are not displayed in the NAPCO NOC web portal (www.NapcoNOC.com). This is intentional and is consistent with how Direct Mode supervision was originally designed.
How Heartbeats Work in Direct Mode
In Direct Mode, the 780 heartbeat signals are transmitted directly from the StarLink communicator to the central station receiver to verify communication and maintain supervision. These heartbeat transmissions are not considered alarm signals and were never intended to be displayed or tracked as successful "OK" events within the NOC.
Unlike 'NOC Mode', where communication activity can be monitored by the NOC website, Direct Mode relies on the central station receiver to acknowledge heartbeat transmissions. In Direct Mode, the StarLink communicator was intentionally designed to communicate directly with the receiver and not to send duplicate heartbeat transmissions to the NOC.
Why Heartbeats Are Not Sent to the NOC
Sending every heartbeat to both the receiver and the NOC would create additional network traffic and processing overhead for the StarLink communicator. To maintain efficiency and rapid system performance, heartbeat transmissions are only sent to the receiver in Direct Mode. This efficient approach is also consistent with other industry solutions. Manufacturers such as DMP and DSC do not provide dealers with visibility into routine heartbeat transmissions when operating in direct-connect modes.
Where Heartbeat Information Can Be Viewed
Depending on the central station configuration, heartbeat activity may be visible in the following locations:
- Central station automation software logs (if the receiver forwards heartbeat events)
- Receiver event logs (if accessible by central station personnel)
Dealers typically do not have direct visibility into heartbeat acknowledgments through the NOC when operating in Direct Mode.
Supervision Failure Monitoring
Although individual 780 heartbeat transmissions are not displayed in the NOC, communication failures are actively monitored.
If the receiver does not acknowledge heartbeats within the programmed polling interval, the central station receiver generates:
- a YC signal (loss of central polling) when communication is lost
- a YK signal (loss of central polling restore) when communication is re-established.
Example:
If the polling interval is configured for 60 minutes, the StarLink communicator sends a 780 heartbeat signal approximately every 25 minutes.
- First 780 heartbeat is sent.
- If it is not acknowledged, no trouble conditions are generated because the StarLink communicator is still within the 60-minute supervision window.
- A second 780 heartbeat is sent.
- If acknowledgments are still not received and the supervision interval is exceeded, the central station receiver generates a YC (loss of central polling) signal.
- After communication is restored, the central station receiver generates a YK signal (loss of central polling restore) signal.
Key Takeaways:
- 780 heartbeat signals are intentionally not displayed in the NOC when a StarLink communicator is operating in Direct Mode.
- In Direct Mode, heartbeat supervision is handled between the StarLink communicator and the central station receiver.
- The absence of 780 heartbeat signals in the NOC does not indicate a communication failure.
- The central station receiver supervises the StarLink communicator via 780 heartbeat signals and will generate a YC signal if heartbeat acknowledgements are missed beyond supervision interval.
- Central station receiver will generate a YK signal when communication is restored.