What is an alarm code 302 in Area 00 for Zone 994?
A Contact ID code 302 on Zone 994 in Area 00 translates to a 'Low System Battery' trouble condition originating from a StarLink communicator. This means that the input voltage is either below the threshold of 9VDC or above 26VDC.
- If the voltage is above 26VDC: Use an SLE-FIRE-VR Voltage Drop Kit
- If the voltage is lower than 9VDC: A different power source of 9VDC or higher is needed
Note: Zone 994 is a 'virtual' zone code and not a physical zone. With many security systems, Zone 994 is specifically used to route hardware system issues from the communicator back to the central station.