How do I set up a FWC-FSLC-SOM1-E Supervised Output Module in place of a NAC Extender with Gemini C-Series (GEMC) control panels (including Firewolf and FireLink panels)?
To set up a FWC-FSLC-SOM1-E Supervised Output Module in place of a NAC Extender with GEMINI GEMC series control panels (including Firewolf and FireLink panels), you will need a fire-rated 24VDC power supply and, possibly, a sync module for the manufacturer of your horn strobes. Your control panel SLC loop will connect to TB3 located on the right side of the FWC-FSLC-SOM1-E module. The 24VDC power supply connects to TB1 on the top two terminals and your horn strobes connects to the next two terminals labeled "Out +/-" (EOL resistor is required for Class B operation). Ensure the jumper located below TB1 is set for Class A or B as desired. Connect the sync module as instructed by its manufacturer. See wiring diagrams below for Class A and Class B wiring.
Class B Wiring:
Class A Wiring: