FAQs
I am trying to program a Bosch radio communicator. Why am I unable to see the options for Modem 2 and Modem 3 formats?
If you have a Bosch radio communicator with the SLE-MF-JMP jumper installed and you are unable to find the options for Modem 2 or Modem 3 (in the Advanced tab under Handshake Configuration), you must update the communicator firmware using firmware for the StarLink models LTBAI or LTBVI, as appropriate.
The firmware files are available for download from https://tech.napcosecurity.com/.