Do I need to perform any changes to the FireLink Fire Alarm Control Panel (FACP) default program?
The FireLink FACP is shipped with a factory default program already set to report to your central station. In general, the additional steps are: Register the radio communicator, connect all field wiring, add resistors to all unused zones and NACs, power the control panel with batteries, log in to the NAPCO NOC website at www.NapcoNoc.com and enter the primary / backup telephone numbers and acount numbers (or the SurGard IP information) and save the changes.
The default zone programming:
- Zone 1 Waterflow, CID Code E113
- Zone 2 Supervisory (Tamper) , CID Code E200
- Zone 3 Pull Station, CID Code E115
- Zone 4 Smoke Detector, CID Code E111
- Zone 5 Conventional Fire Zone, CID Code E110
- Zone 6 Conventional Fire Zone, CID Code E110
- Zone 7 Conventional Fire Zone, CID Code E110
- Zone 8 Supervisory (Cell/IP Communicator Trouble), CID Code E200
- NAC A enabled for Zones 1, 3 - 7
- NAC D enabled for Zone 1 Waterflow