For Dual Path IP Commercial Fire reporting, are there any special requirements for providing backup power to the IT equipment at the premises?
The SLE Dual Path radio communicator is connected to the broadband modem, router and/or switch at the premises. Therefore, to provide standby backup power to these devices, use a UL 1481, UL 864 or UL Listed ITE (Information Technology Equipment) UPS (Uninterruptible Power Supply) to allow these devices to remain powered for a minimum of 24 hours.