Will the StarLink LTE Sole Path and Dual Path communicators generate an indication if a line cut condition is detected?
Yes, the D5 LED will blink 8 times and trip the trouble output.
Sole Path: Firmware version 112.0.2 / 4.1 or higher
- Open circuit on a supervised zone (i.e. supervised fire alarm/trouble configuration on IN2 or IN3).
Dual Path: Firmware version 128.2.57 / 10.1 or higher
- Open circuit on single EOLR zones is detected on IN2, IN3, IN4 or IN5 when programmed for supervision/fire; open circuit on a supervised zone (i.e. supervised fire alarm/trouble configuration on IN2 and IN3), or a Tip/Ring fault.
Note: The StarLink communicator will still indicate a line cut by blinking the D5 LED 8 times if the communicator is set to Backup Mode when jumper 3 is installed.