What is a control panel "cold start", and do I have to perform it during an EPROM Upgrade?
"Cold starting" a control panel resets the control panel back to its original "default" condition, i.e. the state it was in when it left the factory. It clears the control panel of all programming and settings. ALWAYS perform a cold start after replacing the EPROM (see WI2052 for more information).
IMPORTANT: Before replacing an EPROM, always upload the control panel program (to be reâ€downloaded afterward).
How do I perform a cold start?
To cold start the GEM-P816, GEM-P1632 or GEM-P1664 Control Panels:
- In Direct Address Programming Mode, enter the following address:
- Once in Dealer Program Mode, press Reset.
- Enter Dealer Program Mode from keypad #1 (the default Dealer Code is 4 5 6 7 8 9)
- Upload the control panel program (panel firmware versions 11 and lower, enter address 1198; panel firmware versions 30 and higher, enter address 2286)
- Press the ON / OFF button to save.
- Press Reset twice to exit Dealer Program Mode. Verify the keypad display reads: E09-00 Cold Start.
- Download the appropriate program to the control panel
To cold start the GEM-P3200, GEM-P9600 or GEM-X255 Control Panels:
- Upload the control panel program.
- Enter Dealer Program Mode from keypad #1 (the Master Security Code is printed on the silver shield inside the control panel housing).
- Once in Dealer Program Mode, press Reset.
- In Direct Address Programming Mode, enter address 4093.
- Press the ON / OFF button to save.
- Press Reset twice to exit Dealer Program Mode. Verify the keypad display reads: E09-00 Cold Start.
- Download the appropriate program to the control panel.