What are the basic NOC programming steps (http://NapcoNOC.com) when connecting a StarLink Fire Radio to the DACT of an FACP, using dial capture mode reporting?
Check the installation and programming instructions for wiring and other programming options. Be sure all items in the following checklist are performed:
- Telephone numbers are programmed in the "Dealer Entered Programming" section (see following image):
- UL Poll Fail Timeout is set (200 seconds NFPA 2007 service plan; 5 minutes for NFPA 2010 plan; 60 minutes for NFPA 2013 plan or 24hr backup only):
- Input 2 (IN2) is programmed for Supervised Fire Trouble (line cut) and a relay on the Fire Alarm Control Panel (FACP) programmed for Telco Fault, and is connected to Input 2 with a 10K EOLR wired to the relay:
- The central station telephone number ("Telco # for reporting tamper/linecut/parallel inputs") and account number ("Subscriber Account Number") are programmed in the Advanced tab:
- Note: The central station receiver telephone number and account number must be manually entered.
- Input 1 (IN1) is wired to a trouble zone in the FACP.