What is the correct wiring for the MVA-1000 Talking Siren Driver when using both Fire and burglary outputs?
To wire the MVA-1000 to a GEM-P3200 or GEM-P9600 control panel:
- MVA blue wire to the control panel terminal 5 (Burg Out N/O)
- MVA red wire to the control panel Lug E14 (fused battery power)
- MVA black wire to the control panel terminal 14 (Aux Pwr Neg)
If you program all Burglary zones for Burg output and all Fire zones for Pulse Burg Output the result will be the appropriate siren for burg / fire.