Answer:
NO... the keypad data received by the controller will be identical as a 26 bit Prox card. You do not have to Enable the keypad under Readers.
View Answer
Answer:
YES - Remove the reader wiring from the reader port. On the controller, you should read +5V between D0 to Gnd and 5V between D1 to GND.
If you do not measure 5 volts, you will have to replace the board.
View Answer
Answer:
YES - The CA4K will support a 4 or 8 bit burst keypad. In the early days of CA3000, it only supported a 4 bit burst, but eventually it was updated to support either a 4 bit burst, or a 8 bit burst keypad.
View Answer
Answer:
If you are not using a keypad, you must verify the Keypad is NOT enabled under Readers>Door Control.
View Answer
Answer:
1) Max characters allowed on a Magstripe is 75 characters.
...
View Answer
Answer:
If you are not using Door Contacts (Door Sensors), you must set the Door Sensor =0 under Configuration>Readers and then you MUST perform a DATA DOWNLOAD to the panel. This requirement was added into the Continental Software in 2017.
View Answer
Answer:
NO...The Accelaterm does not offer an XY interface. Note: Most newer controllers do not support XY Matrix keypads.
View Answer
Answer:
Yes, the grounds are common between the +5V accessory power Connector and the Reader Port Ground.
View Answer
Answer:
The Toggle mode (Single Swipe) for Relays is supported in the CardAccess 3000, V2.9.88 and V2.11.x.
...
View Answer
Answer:
The Trilogy Networx Panel is a 1 Door (2 Reader) wireless controller. If both readers are used, they must be set up as IN/OUT readers (One on each side of the same door).
...
View Answer
Answer:
If there is too much power being drawn on the +12volts or +5volts, the Continental Controller will beep. If this occurs, remove the keypad or reader immediately.
View Answer
Answer:
The "Double Tap" feature works identical for Wireless Locks with Prox readers and Continental Controllers with the latest firmware as of V2.11.84 and all versions of the CA4K software. For this function to work, you must select "Double read holds...
View Answer
Answer:
VERY IMPORTANT: If possible, name the new computer the same name as the old computer name. This will eliminate some of the most difficult steps in this procedure.
...
View Answer
Answer:
Like any electronic device, it's always recommended to cycle the power on the reader/keypad.
View Answer
Answer:
Some PIV readers and PIV badges are dual technology. A dual technology PIV reader can read the PIV section of the badge and also read another technology in the badge such as 125KHZ. The reader will beep twice and the CardAccess 3000 will display...
View Answer
Answer:
Yes...Virtual Inputs are available on the 8 and 16 door Accelaterm. They are only available on the first 8 readers on both models (8 or 16 Door). The virtual input numbers for the first eight readers map identical to the Turbo Superterm and...
View Answer
Answer:
Note: An 8 door Accelaterm can have up to 3 I/O expansion boards connected to it. A 16 door Accelaterm can only have 2 I/O expansion boards connected to it. Each I/O expansion board contains 16 additional inputs and 16 additional...
View Answer
Answer:
Summary: This error message means there is a record of the badge in the database, but the badge does not belong at any reader on the panel.
...
View Answer
Answer:
When an external voltage is supplied to a reader/keypad, you MUST common the grounds between the power supply ground and the ground on panel.
View Answer
Answer:
There are many types of keypads available, which determine the different modes available. Below are 4 different supported modes.
...
View Answer
Answer:
For a photo to pop-up, the alert must be configured to come into the Alert grid (bottom half of screen). If the alert is configured to go directly to the event grid (top half of screen), the photo will not pop up. By default, valid badges are...
View Answer
Answer:
The following are some reasons why this might occur after adding a new panel to the software"
...
View Answer
Answer:
Verify the door sensor is working correctly. If there is no physical door contact, you MUST set the "Door Sensor" setting to zero under "Configuration>Readers>Door Control".
View Answer