Answer:
No, the control panel may utilize zones 1-8 on the FIM module or in the SLC loop, but not both, as the control panel will be unable to determine where the zone is located. With FireLink control panels, there are 2 options:
...
View Answer
Answer:
When using horns or horn/strobes with the GEMC and FireLink FACPs, you must use a NAC that is not used by other (non-CO) zones.
...
View Answer
Answer:
Program for dry contact to change state when a fire alarm or a panel trouble condition occurs. The following is for an additional annunciation panel (not a keypad):
...
View Answer
Answer:
Yes! When a fire alarm activates, the Heating, Ventilation, and Air Conditioning (HVAC) system is generally required to be shut down to prevent the spread of smoke and fire. After a fire alarm-triggered shutdown, the HVAC system does not...
View Answer
Answer:
NFPA 72 and UL 864 prohibit remote downloading to a Fire Alarm Control Panel unless a qualified technician is physically at the control panel installation site. To ensure a technician is on site, the Fire system keypad must first be unlocked...
View Answer
Answer:
Models: All FireLink, Firewolf* and GEMC* Fire Panels (FL-xxx, FLX2-xxx, GEMC-FW-xxx, GEMC-COMBOxxx)
...
View Answer
Answer:
To set up a FWC-FSLC-SOM1-E Supervised Output Module in place of a NAC Extender with GEMINI GEMC series control panels (including Firewolf and FireLink panels), you will need a fire-rated 24VDC power supply and, possibly, a sync module for the...
View Answer
Answer:
Yes. To provide constant power for magnetic locks and other powered devices, you can program either the FireLink control panel NAC D integral output or you can program the NAC Extender GEMC-NAC7 PC board, as follows:
...
View Answer
Answer:
An E97 trouble is an SLC trouble that can be caused by many things. To determine the exact trouble condition, launch PCD-Windows Quickloader and examine the status of the system. In the Status / Control screen, open the SLC tab. The devices in...
View Answer
Answer:
As detailed below, mount the GEMC-FW-SLC module to the HW1489 Battery Shelf with the hardware provided.
...
View Answer
Answer:
The Napco FWC-FSLC-CZM Conventional Zone Module allows the control panel fire SLC (Signaling Line Circuit) loop to interface with and monitor two-wire conventional detectors or pull stations. When used with the GEMC-F8ZCPIM Conventional 8 Fire...
View Answer