Filter By Brand

FAQs By Category

Results Per Page | Showing 1-20 of 20 Results | 1

Can I program my FireLink / GEMC fire alarm system to allow an HVAC system to be independently overridden and restarted after a fire alarm HVAC shutdown?

Answer:
Yes!  When a fire alarm activates, the Heating, Ventilation, and Air Conditioning (HVAC) system is generally required to be shut down to prevent the spread of smoke and fire.  After a fire alarm-triggered shutdown, the HVAC system does not...

With the Gemini C-Series (GEMC) control panels, can I program horns and strobes to silence simultaneously?

Answer:
Yes.  As shown below, launch PCD-Windows Quickloader, open NAC/Output Assignment > NAC/Output Options and add a check to Horn/Strobe Simultaneous Silence.

How can I use my NAPCO Gemini GEM-P3200, GEM-P9600, or GEM-X255 burglary alarm control panel to automatically turn off a water shut off valve controller--but only when I arm the system and leave the premises?

Answer:
The Gemini GEM-P3200, GEM-P9600, or GEM-X255 burglary alarm control panels can be programmed to provide a voltage trigger or a dry contact closure using a low current relay.  This relay can be used to trigger your water valve controller to close...

How do I set up a FWC-FSLC-SOM1-E Supervised Output Module in place of a NAC Extender with Gemini C-Series (GEMC) control panels (including Firewolf and FireLink panels)?

Answer:
To set up a FWC-FSLC-SOM1-E Supervised Output Module in place of a NAC Extender with GEMINI GEMC series control panels (including Firewolf and FireLink panels), you will need a fire-rated 24VDC power supply and, possibly, a sync module for the...

If I use a Gemini C-Series (GEMC) control panel as a "Burg-only" control panel, do I have to add resistors to all NAC circuits?

Answer:
Yes.  As shown in the image below, if you are using a Gemini C-Series (GEMC) Control Panel as a "Burg-only" control panel, you MUST add resistors to all NAC circuits as they are all supervised.  Remember, Area 1 will always be a Fire Area,...

With FireLink, GEMC and Firewolf control panels, what is an 'E97' trouble and how can I determine its cause?

Answer:
An E97 trouble is an SLC trouble that can be caused by many things. To determine the exact trouble condition, launch PCD-Windows Quickloader and examine the status of the system. In the Status / Control screen, open the SLC tab. The devices in...

How do I program my Gemini C-Series (GEMC) and Firewolf control panel NAC circuits to synchronize System Sensor and/or Wheelock strobes or horn/strobes?

Answer:
Program your Fire zones for the required on-board panel NACs (NAC A and/or NAC D for 32 and 96 zone control panels; NAC A and B or C or D for 128 and 255 zone control panels, shown below).
...

How do I wire and program supervised NAC extenders with my Gemini C-Series (GEMC) and Firewolf control panel?

Answer:
Some fire installations require additional NAC circuits beyond the integral NACs provided on the control panel. All Gemini C-Series (GEMC) and Firewolf control panels have the ability to synchronize up five supervised NAC extenders (using System...

I found older horns and/or 4-wire horn strobes installed in my Gemini C-Series (GEMC) system. How do I wire and program my GEMC control panel to have the panel generate the required Temporal 3 cadence?

Answer:
When retrofitting older GEMC / Firewolf control panels, installers may find older horns and/or 4-wire horn strobes installed.  Unlike the newer smart devices, these older NAC devices may not include a pre-programmed Temporal 3 cadence....

How do I program the Test Timer feature with the GEMC control panels?

Answer:
With Test Timer programmed, an automatic test report is transmitted to the central station on the scheduled day(s) at the scheduled time.  Program Test Timer as follows:
...

What are the required control panel configuration settings when installing an Elevator Recall system?

Answer:
Control panel features and programming may vary depending on applicable local codes and when integrated with other fire protection systems (such as a sprinkler system).  Consult with your AHJ for all local code requirements.
...

How do I set up my GEMC control panel for "elevator recall" using the GEMC-F8ZCPIM module and the RM3008 relay?

Answer:
The following details the generic control panel configuration settings required when installing an Elevator Recall system. Control panel features and programming may vary depending on applicable local codes and when integrated with other fire...

Is more than one Fire Area allowed with the Gemini C-Series (GEMC) control panels?

Answer:
No, the Gemini C-Series (GEMC) Firewolf control panels support one (1) Fire Area only, although up to seven (7) GEMC-FK1 Fire keypads may be programmed into Area 1.  

How can I resolve a System Trouble "E14" on GEMC-Series Panels when used with a FWC-FSLC-SOM1 Supervised Output Module or a FWC-FSLC-DUCT Duct Detector?

Answer:
If a system trouble "E14" appears, and pressing RESET on the keypad will not clear the trouble, a likely reason could be the SOM and/or Duct Detector are programmed for "Reset-able" in the NAC Output/Assignment screen in PCD-Windows Quickloader...

Our Fire Department will not let us install any system that requires codes to reset.

Answer:
The GEMC series control panels support the "keyswitch unlock" feature, which replaces user code entry.  Simply turn the keyswitch and it will "unlock" the keypad, allowing Silence, Reset or advanced operations (such as programming).  In...

40 Results Per Page | Showing 1-20 of 20 Results | 1