Date Added: 11/5/20
If using MODEM II, MODEM IIe or MODEM IIIe2 Reporting Formats:
When the fire alarm control panel (FACP) is reporting with the formats MODEM II, MODEM IIe or MODEM IIIe2, the SLE-MF-JMP jumper must be inserted into J8 (with the white line towards the left side of the Dual Path communicator as shown in this document).
Do NOT use this SLE-MF-JMP jumper when the FACP uses other reporting formats.
Posted in [Installation Manuals]
Tags:
Date Added: 3/12/24
The Bosch/Radionics Modem II and Modem III re-porting formats are dial captured from the alarm control panel in the same manner as CID and 4/2 formats.
These formats have been evaluated by ETL/Intertek in the following models:
SLE-LTEVI-CFBPS, SLE-LTEVI-CFB, SLE-LTEAI-CFBPS, SLE-LTEAI-CFB, SLE-FNI-FIRE, SLE-FNI-CFB, SLE-FNI-CFB-PS, SLE-LTEVI-FIRE, SLE-LTEAI-FIRE, SLE-LTBVI-FIRE, SLE-LTBVI-CFB, SLE-LTBVI-CFBPS, SLE-MAXVI-CFBPS, SLE-MAXVI-CFB, SLE-MAXAI-CFBPS, SLE-MAXAI-CFB, SLE-MAXVI-FIRE, SLE-MAXAI-FIRE, SLE-MAX2-FIRE, SLE-MAX2-CFB and SLE-MAX2-CFBPS.
Posted in [Installation Manuals]
Tags: