Date Added: 3/5/20
New York City Certificate of Approval (StarLink SLE Series Dual Path Communicators, LTE Network, on AT&T and Verizon)
SLE Series Dual Path Communicators on AT&T:
SLE-LTEAI-CFB-PS SLE-LTEAI-CFBSLE-LTEAI-FIRE
SLE Series Dual Path Communicators on Verizon:
SLE-LTEVI-CFB-PSSLE-LTEVI-CFBSLE-LTEVI-FIRE
FDNY Certificate of Approval # 6317Expires on March 1, 2023.
Date Added: 4/22/21
Connecting a StarLink Communicator as a Back Up to a Telephone Line.
For installations that require the FACP to communicate through the telco line with cellular backup, the telephone line must be connected to the FACP Telco 1 (DACT 1) and the StarLink communicator TELCO SECONDARY to the FACP Telco 2 (DACT 2), as detailed in this Tech Tip.
Date Added: 5/21/19
NAPCO StarLink Commercial Fire Communicator SLE-LTEVI-CFB-PS & SLE-LTEAI-CFB-PS (Dual Path) Dial Capture Wiring Diagram (PDF format).
NAPCO StarLink Commercial Fire Communicator SLE-LTEVI-CFB-PS & SLE-LTEAI-CFB-PS (Dual Path) Input Wiring Diagram (PDF format).
NAPCO StarLink Commercial Fire Communicator SLE-LTEVI-CFB-PS & SLE-LTEAI-CFB-PS (Dual Path) Dial Capture Wiring Diagram (DWG format).
NAPCO StarLink Commercial Fire Communicator SLE-LTEVI-CFB-PS & SLE-LTEAI-CFB-PS (Dual Path) Input Wiring Diagram (DWG format).
Date Added: 12/28/23
Dual Path Input Reporting Programming
By default, StarLink dual path communicator inputs 2 through 5 are programed as: IN2 (Trouble), IN3 (Alarm), IN4 (Supervisory) and IN5 (Waterflow).
To program these options, refer to this Tech Tip.