What is the first Relay number while using an I/O Relay Expander on an Accelaterm?
For both an 8 and 16 door Accelaterm, the first relay number on the Accelaterm I/O Expander unit is #17.
Note: The relay numbering on the Accelaterm controller is 1 to 16 and #73 for the console relay.
The relay numbering for the Accelaterm relay I/O expansion is :
1st I/O board - 17 to 32
2nd I/O board - 33 to 48
3rd I/O board - 49 to 64