FAQs
Can you explain how to enroll GEMC SLC fire devices?
On-Site Enrollment of SLC Detectors
This method allows the enrollment of the devices on-site, after the installation is completely wired and powered. The control panel program must be loaded into the control panel, with the SLC devices programmed in consecutive zones.
1. Unlock the GEMC-FK1 Fire keypad (enter your Master Code, then press ENTER).
2. Re-enter your Master Code, then press MENU. Press MENU until Enable Programming appears on the keypad display. Press ENTER and a system trouble E28 appears (PC Error Check Required).
3. Re-enter your Master Code, then press MENU. Press MENU until CF Dealer Prog Mode appears on the keypad display, then press ENTER.
4. Press MENU until ZN# DevID+CS P R appears on the keypad display.
5. Enter the starting zone number.
6. Press SILENCE to enter batch enroll mode (the word ENROLL appears on the keypad display).
7. Go to the physical location of the first detector and install the detector onto its base.
8. The keypad displays the device number to confirm the detector is assigned to the correct zone.
9. Repeat for each detector in the system.
10. When finished, press RESET twice to exit Program Mode.
11. The panel will reinitialize and a system trouble E28 will again appear (PC Error Check Required). Upload the current program, run an error check and download the program back to the control panel.
In-Office Enrollment of SLC Detectors
This method allows the enrollment of the devices "in the office", before the devices are taken to the job site for installation. It is recommended to use the control panel that will be installed at the site, together with the SLC module(s) to be installed.
1. Unlock the GEMC-FK1 Fire keypad (enter your Master Code, then press ENTER).
2. Re-enter your Master Code, then press MENU. Press MENU until Enable Programming appears on the keypad display. Press ENTER and a system trouble E28 appears (PC Error Check Required).
3. Re-enter your Master Code, then press MENU. Press MENU until CF Dealer Prog Mode appears on the keypad display, then press ENTER.
4. Press MENU until ZN# DevID+CS P R appears on the keypad display.
5. Press SILENCE to enter the Quick Method batch enroll mode.
6. Enter the starting zone number.
7. Install detector onto a base.
8. The keypad displays the device number and a confirmation that it has been assigned to a zone XX.
9. Remove the detector from the base.
10 Write the zone number and a description of its location on the device box, and place the detector inside.
11. Install a new detector onto a base.
12. Repeat steps 7-12 for each detector.
When finished, an installation team can take the enrolled detectors to the site and install each device into its proper location, as per the zone number and location description written on each device box.