FAQs
What are the power requirements for StarLink Fire communicators that are powered by the control panel, for example, models SLE-LTEV-FIRE, SLE-LTEA-FIRE, SLE-LTEVI-FIRE and SLE-LTEAI-FIRE?
The StarLink Commercial Fire communicators are very versatile; they are compatible with a multitude of fire alarm control panels. Regulated (filtered) voltage between 12VDC and 24VDC is required. If your voltage is above 26.5VDC, we recommend using a CFB-PS model.
Important: The StarLink Fire communicators will NOT operate properly if connected to "Resettable" power. This includes annunciator power, NAC circuits, or fire device circuits.
If regulated power above 26.5VDC (or non-resettable power) is not available, you must use a model with a power supply (models ending with CFB-PS).