With the Alarm Lock exit door lock models 715 and 265, in the Control Box I correctly measure 12VAC into terminals 1 and 2 (TS1). Why do the corresponding terminals 1 and 2 on TS2 measure zero voltage?
The Control Box is designed to block voltage until the Lock Assembly is fully wired. Terminals 1 and 2 on TS2 measure zero voltage because you have not yet wired terminals 1-5 in the Lock Assembly.